Cat EGP Switchgear
EGP (Emergency Generator Paralleling) switchgear is used for paralleling multiple generators that are not directly connected to a utility source.
Configuration
Configurable PLC based switchgear capable of controlling and monitoring multiple generator sets, tie and load breakers in conjunction with downstream transfer switches for standby or emergency applications
Modes of Operation
Multi-unit Island and multi-unit standby mode with optional redundant controls and components.
Application
LV and MV (208V - 38 kV)
Specification
Value
Configuration
Configurable PLC based switchgear capable of controlling and monitoring multiple generator sets, tie and load breakers in conjunction with downstream transfer switches for standby or emergency applications
Modes of Operation
Multi-unit Island and multi-unit standby mode with optional redundant controls and components.
Application
LV and MV (208V - 38 kV)
Specification
Value
ANSI Protective Devices
15/25, 27/59, 81 O/U, 32, 40, 50, 51
Specification
Value
Certifications
IBC, CBC, UBC & OSHPD Certified
Control Panel Enclosure
NEMA 1 or NEMA 3R Freestanding Construction
Operating Temperature
0°C to 50°C
Storage Temperature
-20°C to +60°C
Low Voltage Standards
NEMA SG-5, CSA, ANSI C37.51, ANSI C37.20.1, UL 1558 or UL 891, NFPA 110, NFPA 99 and NFPA 70
Medium Voltage Standards
NEMA SG-5, ANSI / IEEE C37.20.2, CSA-C22.2 No. 31-M89, EEMAC G8-3.2, NFPA 70, NFPA 99 and NFPA 1110
- High Speed Supervisory Network
- Automatic Start/Stop
- Automatic “Dead Bus” Coordination
- Programmable Load Shed / Load Add Functions
- Networked Engine Communications
- Generator Protection
- Engine Tuning
- Mode Selection
- Selectable Auto/ Manual Control
- Password Protection for Protective Settings and Setup
- Load/No Load Test
- Touch Screen (HMI) Display
- NFPA 99/110 Compliant Alarm
- Annunciation with Audible Horn
- Engine Control mimic Screen with gauges for RPM, DC Battery Voltage oil Pressure, Engine Coolant temperature, Engine Hours, Number of starts
3516B DGB™ (50 Hz)
3516 (60 Hz) with Upgradeable Package
3516B DGB™ (60 Hz)
3512B (50 Hz)
C32 (50 Hz)
C175-20 (50 Hz)
C175-16 Tier 4 Final (60 Hz)
3512B (60 Hz) 1500 kW with Upgradeable Package
3512C (60 Hz)
3516E (50 Hz)
3512 (60 Hz) with Upgradeable Package
3516B (60 Hz) with Upgradeable Package
3516 (50 Hz)
3512 (50 Hz)
C175-16 (50 Hz)
C27 (60 Hz)
3516B (50 Hz)
3516C Tier 4 Final (60 Hz)
Cat Switchgear