Home > Products > Compare
COMPARE MODELS
Our product comparison allows for the review of up to 3 related models technical specifications at the same time.
ATS ATC Breaker / Contactor
ATC-900 CONTROLLER
ADD MODEL
ADD MODEL
Rating Range
120 to 600V, single phase and three phase @ 50/60 Hz
Na
Na
Transfer Type
Switch application dependent
Na
Na
Switch Type
Switch application dependent
Na
Na
Input Control Voltage
120Vac (50/60 Hz) (operating range 65 to 160 Vac)
Na
Na
Voltage Measurements of Utility
Source 1, Source 2 and Load
(VAB, VBC, VCA for Three Phase System)
Na
Na
Voltage Measurement Range
0 to 700 Vac
Na
Na
Voltage Measurement Accuracy
+/-1% of full scale
Na
Na
Frequency Measurements Of
Source 1 and Source 2
Na
Na
Frequency Measurement Range
40 Hz to 80 Hz
Na
Na
Frequency Measurement Accuracy
+/- 0.1 Hz
Na
Na
Undervoltage Dropout
Breaker Style 50 to 97% of Nominal System Voltage
Contactor Style - 78 to 97%
Na
Na
Undervoltage Pickup
(Dropout +2%) to 99% of Nominal System Voltage
Na
Na
Underfrequency Dropout Range
90 to 97% of Nominal System Frequency
Na
Na
Underfrequency Pickup Range
(Dropout +1 Hz) to 99% of Nominal System Frequency
Na
Na
Overfrequency Dropout Range
103 to 110% of Nominal System Frequency
Na
Na
Overfrequency Pickup Range
101% to (Dropout +1 Hz) of nominal system frequency
Na
Na
Operating Temperature Range
-20 to 70 degree C (-4 to +158 degree F)
Na
Na
Operating Humidity
Up to 90% Relative Humidity (non-condensing)
Na
Na
Enclosure Compatibility
  • NEMA 12 (std mounting)
  • NEMA 3R
  • UV Resistant Faceplate
  • Na
    Na
    System Voltage Application
    120 to 600 Vac (50/60 Hz) (single or three phase)
    Na
    Na