ATS MX Contactor
MX350 Controller
ADD MODEL
ADD MODEL
Voltage Unbalance on Dropout for Source 1 and Source 2
5 to 20% of nominal
Na
Na
Delay NeutralTransition Time Delays (DT,DW)
0-10 minutes
Na
Na
Control Power
120 VAC
Na
Na
Undervoltage Dropout for Source 1 and Source 2
75-99% of nominal
Na
Na
Undervoltage Restore for Source 1 and Source 2
85-100% of nominal
Na
Na
Overfrequency Dropout for Source 1 and Source 2
50.1 - 63 Hz
Na
Na
Source Sensing
120 - 690 VAC +/- 1% of nominal voltage (+/- .05 Hz, +/-.5 A)
Na
Na
Delay for Engine Cool Down (U)
0-60 minutes
Na
Na
Underfrequency Restore for Source 1 and Source 2
45 - 59.5 Hz
Na
Na
Load Control Relay Contacts (2)
0-259 minutes
Na
Na
Overvoltage Dropout for Source 1 and Source 2
105 - 110% of nominal
Na
Na
Voltage Unbalance for Restore for Source 1 and Source 2
4 to 19% of nominal
Na
Na
Storage Temperature
(-40˚C - 90˚C )
Na
Na
Underfrequency Dropout for Source 1 and Source 2
45 - 59.9 Hz
Na
Na
Overfrequency Restore for Source 1 and Source 2
50 - 62.9 Hz
Na
Na
Delay Transfer to Nonpreferred Source (W)
0-5 minutes
Na
Na
Operating Temperature Ambient
(-20˚C to 50˚C)
Na
Na
Communications Interface - Optional
Serial RS-485 upt to 115.2 Kbps or TCP/IP (10/100 base-T)
Na
Na
Overvoltage Restore for Source 1 and Source 2
103 - 108% of nominal
Na
Na
Load Control Relay Contacts (1)
rated for 10A @ 24VDC or 120VAC
Na
Na
Rating Range
Switch Dependent
Na
Na
Transfer Type
Application Dependent
Na
Na
Switch Type
Application Dependent
Na
Na